Specifications and dimensions EASYAIR®

with rotary heat exchanger

TypeAirflow rate - efficiency - sound level*Specific fan power**Base unit***
MinimumNominal valueMaximumSupply airExhaust airL x W x H in mm
RO-01650 m³/h - 90% - 79 dB(A)1,350 m³/h - 82% - 79 dB(A)1,700 m³/h - 79% - 81 dB(A)847 W/m³ x s630 W/m³ x s1,530 x 712 x 953
RO-021,000 m³/h - 90% - 81 dB(A)2,000 m³/h - 83% - 84 dB(A)2,600 m³/h - 79% - 86 dB(A)861 W/m³ x s621 W/m³ x s1,530 x 865 x 1,259
RO-031,500 m³/h - 90% - 81 dB(A)3,000 m³/h - 82% - 82 dB(A)3,800 m³/h - 79% - 84 dB(A)779 W/m³ x s562 W/m³ x s1,606.5 x 1,018 x 1.259
RO-042,000 m³/h - 90% - 80 dB(A)4,000 m³/h - 83% - 85 dB(A)5,100 m³/h - 79% - 88 dB(A)749 W/m³ x s556 W/m³ x s1,759.5 x 1,171 x 1,565
RO-052,700 m³/h - 90% - 80 dB(A)5,400 m³/h - 82% - 88 dB(A)6,500 m³/h - 80% - 91 dB(A)744 W/m³ x s561 W/m³ x s1,759.5 x 1,324 x 1,565
RO-063,300 m³/h - 88% - 82 dB(A)6,300 m³/h - 80% - 90 dB(A)7,500 m³/h - 78% - 94 dB(A)783 W/m³ x s619 W/m³ x s1,759.5 x 1,324 x 2,177
RO-074,200 m³/h - 90% - 81 dB(A)8,400 m³/h - 82% - 90 dB(A)10,200 m³/h - 80% - 93 dB(A)778 W/m³ x s556 W/m³ x s1,989 x 1,630 x 1,871
RO-085,000 m³/h - 88% - 82 dB(A)10,000 m³/h - 80% - 88 dB(A)11,000 m³/h - 79% - 80 dB(A)727 W/m³ x s545 W/m³ x s2,142 x 1,630 x 2,177
RO-096,000 m³/h - 90% - 81 dB(A)12,000 m³/h - 83% - 91 dB(A)13,000 m³/h - 81% - 92 dB(A)689 W/m³ x s511 W/m³ x s2,142 x 1,936 x 2,177

* Airflow rate: External pressure loss supply air 300 Pa, exhaust air 250 Pa. Efficiency: Efficiency of heat recovery according to EN (DIN) 308 (dry) Sound power level in the air supply duct with dampers.

** Specific fan power (SFP) according to EnEV at nominal airflow rate and external air duct pressure losses supply air 300 Pa, exhaust air 250 Pa, with dampers and filters (F7/M5)

*** The optional connection frame increases the length of the unit by 65 mm on both sides.

 

Specifications and dimensions EASYAIR®

with plate heat exchanger

TypeAirflow rate - efficiency - sound level*Specific fan power**Base unit***
MinimumNominal valueMaximumSupply airExhaust airL x W x H in mm
PL-01650 m³/h - 84% - 78 dB(A)1,350 m³/h - 81% - 78 dB(A)1,700 m³/h - 79% - 80 dB(A)741 W/m³601 W/m³2,142 x 712 x 953
PL-021,000 m³/h - 84% - 79 dB(A)2,000 m³/h - 81% - 83 dB(A)2,500 m³/h - 80% - 85 dB(A)748 W/m³600 W/m³2,142 x 1,018 x 953
PL-031,500 m³/h - 90% - 80 dB(A)3,000 m³/h - 87% - 82 dB(A)3,700 m³/h - 86% - 84 dB(A)761 W/m³542 W/m³2,524.5 x 1,018 x 1,259
PL-042,000 m³/h - 90% - 79 dB(A)4,000 m³/h - 87% - 83 dB(A)5,000 m³/h - 80% - 87 dB(A)715 W/m³516 W/m³2,524.5 x 1,324 x 1,259
PL-052,500 m³/h - 84% - 80 dB(A)5,000 m³/h - 80% - 87 dB(A)6,200 m³/h - 79% - 90 dB(A)736 W/m³612 W/m³2,601 x 1,630 x 1,259

* Airflow rate: External pressure loss supply air 300 Pa, exhaust air 250 Pa. Efficiency: Efficiency of heat recovery according to EN (DIN) 308 (dry) Sound power level in the air supply duct with dampers.

** Specific fan power (SFP) according to EnEV at nominal airflow rate and external air duct pressure losses supply air 300 Pa, exhaust air 250 Pa, with dampers and filters (F7/M5)

*** The optional connection frame increases the length of the unit by 65 mm on both sides.